Loading…
Water level
Reading against the twins
measured minus the twins' median, cmTimes in your time zone.
Only this gauge?
each input gauge against its own twins, same periodThe inputs' own verdicts lag (they wait for their own late inputs), so the comparison is made at the newest step where most of them have one.
0 means inside the twins' range; 2 means two tolerances outside it (the axis stops at ±10). Many lines leaving 0 together point to a shared event (rain, a release, ice); this gauge leaving alone points to the gauge itself.
In this period
Twin agreement
Connected gauges
This gauge's twins read these gauges; the gauges below read this one.
Inputs
Read by · the gauges whose twins read this one
How to read this
Every 15 minutes MEDUSA rebuilds this gauge's water level with its own AI digital twins, from the gauges that tell most about it, near or far. Their spread is the twins' range; their middle is the median.
- Fine: the reading lies within the twins' range, or outside it by less than the gauge's tolerance while staying within its usual spread.
- Slight suspicion: outside the twins' range by more than the tolerance, but within the usual spread.
- Strong suspicion: outside the twins' range, by any amount, and outside the usual spread as well.
- No reading: the gauge reported nothing for that step. The newest steps can wait for gauges that publish late; they fill in at the next hourly run. The tolerance is set for this gauge by how closely its twins follow it; the usual spread is how far its readings normally stray from the twins in recent weeks.
A sensor fault, drift, a dam release or ice can all move a gauge away from its twins; "Only this gauge?" above shows whether its input gauges moved too.